Monitoring functions
SIMOCODE pro
GWA 4NEB 631 6050- 22 DS 03
5-7
5.2.3 I< (lower limit)
Trip level, warning level
When monitoring current limits I< (lower limit), two different response
levels (trip level/warning level) can be parameterized and monitored. If the
current of the phases (I_max) drops below the response level, current limit
monitoring responds.
Trip level and warning level activity
The trip level/warning level is only effective when the motor is running, the
start-up procedure has been completed and there is no test position
feedback (TPF) (run+).
Response at trip level
Here you can set how SIMOCODE pro should respond when the trip level is
undershot:
See also "Tables of responses of SIMOCODE pro" in Chapter "Important
information".
Table 5-5: "Warning level" response for monitoring current limits I<
Response at warning level
Here you can set how SIMOCODE pro should respond if the warning level is
undershot:
See also "Tables of responses of SIMOCODE pro" in Chapter "Important
information".
Table 5-6: "Warning level" response for monitoring current limits I<
Hysteresis
Here you can set the hysteresis for the current limits I< (lower limit):
Trip level: 0 to 1020% of I
s
in 4% increments
Warning level: 0 to 1020% of I
s
in 4% increments
Response Trip level
Deactivated X
Signaling X
Warning -
Tripping X
Delay 0 - 25.5 s (0.5 s
)
Response Warning level
Deactivated X
Signaling X
Warning X
Tripping -
Delay 0 - 25.5 s (0.5 s
)
Hysteresis 0 to 15% of the threshold value in 1% increments
Default: 5 %