System description
SIMOCODE pro
1-22 GWA 4NEB 631 6050-22 DS 03
1.5.7 Operating, service and diagnostic data
SIMOCODE pro supplies a large amount of detailed operating, service and
diagnostic data.
Operating data
Motor switching state (ON, OFF, LEFT, RIGHT, SLOW, FAST), derived from the
current flow in the main circuit; thus, feedback via auxiliary contacts of circuit
breakers and contactors is not necessary
Current in phases 1, 2 and 3 and maximum current in % of set current
Voltage in phases 1, 2 and 3 in V
2)
Active power in W
2)
Apparent power in VA
2)
Power factor in %
2)
Phase unbalance in %
Phase sequence
2)
Temperature in the sensor measuring circuits 1, 2 and 3, and maximum
temperature in K
1) 4)
Actual analog signal values
1) 5)
Time to trip in s
Thermal motor model in %
Remaining cooling down period of the motor in s, etc.
It is possible to adapt the units via the device-internal conversion of
individual measured values with the help of the logic modules (calculators)
provided by SIMOCODE pro V. For example, the temperature recorded by
SIMOCODE pro can be calculated in either °F or °C and transmitted to the
automation system via PROFIBUS.
Service data
Among other things, SIMOCODE pro provides the following relevant data
for maintenance:
Number of motor operating hours, also resettable
Motor stop times, also resettable
Number of motor starts, also resettable
Number of permissible starts remaining
Number of overload trips, also resettable
Feeder power consumption in kWh, also resettable
3)
Internal feeder comments stored in the device, e.g. information regarding
maintenance events, etc.
Safety-oriented tripping monitoring in h, also resettable
1) When using basic unit 2
2) When using basic unit 2 with current/voltage measuring module
3) When using basic unit 2 (from version *E03*) with
current/voltage measuring module
4) Additional temperature module required
5) Additional analog module required

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000