Short instructions for configuring a reversing starter
SIMOCODE pro
2-10 GWA 4NEB 631 6050-22 DS 03
2.4 Extending the reversing starter with a control station
via PROFIBUS DP
In this section
In this section you will find out how the previously configured example can
be extended by one control station via PROFIBUS DP. You can switch
between the local control station (local) and PLC/PCS (remote). Thus,
SIMOCODE pro can be controlled locally via the buttons, as well as via
PLC/PCS.
The necessary connections are preset as factory defaults in
SIMOCODE pro. Therefore, you only have to set the PROFIBUS DP address
for SIMOCODE pro so that it can be recognized correctly as a DP slave on
the PROFIBUS DP.
Prerequisites
The following prerequisites must be fulfilled:
The motor is switched off
The supply voltage for the basic unit is switched on. The "Device" LED lights
up green
You have connected the basic unit to the PROFIBUS DP. The PROFIBUS DP
interface is on the front side (9-pole SUB-D socket)
SIMOCODE pro is integrated with your automation system.
Further information on integrating DP slaves can be found in the automation
system documentation.
Setting the PROFIBUS DP Address
First, set the PROFIBUS DP address of the basic unit.
The following options are available:
Via the addressing plug
Via SIMOCODE ES.