Logic modules
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
11-9
Note
The actual value remains the same
- During parameterization or failure of the supply voltage
- If there are simultaneous input signals at input + and input –.
Note
The output is always 0 if a reset is pending.
Settings
Counters 1 to 4 - Description
Input + Increases the actual value by 1.
Activation by any signal
(any sockets
e.g. device inputs, control bits from PROFIBUS DP, etc.)
Input – Decreases the actual value by 1.
Activation by any signal
(any sockets
e.g. device inputs, control bits from PROFIBUS DP, etc.)
Reset Resets the counter to 0 (count value and output)
Activation by any signal
(any sockets
e.g. device inputs, control bits from PROFIBUS DP, etc.)
Limit The maximum value that can be reached when counting and where
the counter issues an output signal.
Range: 0
- 65535
Table 11-4: Counter settings