Logic modules
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
11-11
Note
The response of the plugs of all timers (input, reset) has been completely
changed to level-active for basic unit 1 from version *E05* and higher and
basic unit 2 from version *E03* and higher. Use of an unchanged parameter
file utilizing integrated timers may thus result in a different response if such
basic units are used. For example, if "Fixed level - '1'" is set at the timer
input, the timer function is automatically restarted after the timer reset
occurs. However, in timers with the parameterized type = "Fleeting closing"
there is no change in the response.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000