Mounting, wiring, interfaces
SIMOCODE pro
13-20 GWA 4NEB 631 6050-22 DS 03
Temperature module pin assignment
The following table shows the pin assignment of the removable terminals:
Table 13-8: Pin assignment of the removable terminals of the temperature module
You can connect up to three 2-wire or 3-wire temperature sensors.
• 2-wire temperature sensors:
Bridge the T2 terminals with the T3 terminals.
• 3-wire temperature sensors.
Assign terminals 56 and 57 doubly when three sensors are used.
Connection Assignment
Upper terminals
50 Input T3, temperature sensor 1
51 Input T3, temperature sensor 2
52 Input T3, temperature sensor 3
53 Input T2, temperature sensor 1
54 Input T2, temperature sensor 2
55 Input T2, temperature sensor 3
Lower terminals
56 Input T1, temperature sensor 1 to 3
57 Input T1, temperature sensor 1 to 3
PE System shielding
READY
TM
3UF7 700–1AA00–0
G/YYMMDD
*
Exx
*
50
1T3
51
2T3
52
3T3
53
1T2
54
2T2
55
3T2
56
T1
57 PE

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals