5.9 Control module ”HLA module”
5-149
Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
2 pressure sensors can be connected per axis
S X111: Axis 1 (sensor 1A, 1B)
S X112: Axis 2 (sensor 2A, 2B)
Table 5-23 Connectors X111, X112; 15–pin D–Sub socket connectors
Pin X111 X112 Type
1)
Function
1 P24DS P24DS O Supply, pressure sensor with external +24 V
2 P24DS P24DS O Supply, pressure sensor with external +24 V
3 – – – not assigned
4 – – – not assigned
5 M24EXT M24EXT O Supply, pressure sensor with external 0 V
6 – – – not assigned
7 – – – not assigned
8 – – – not assigned
9 M24EXT M24EXT O Supply, pressure sensor with external 0 V
10 M24EXT M24EXT O Supplementary pin for jumper, pins 10–11 for
3–conductor connection
11 PIST1BN PIST2BN I Analog actual value signal, reference ground
12 PIST1BP PIST2BP I Analog actual value signal, max. range 0...10 V
13 M24EXT M24EXT O Supplementary pin for jumper, pins 13–14 for
three–conductor connection
14 PIST1AN PIST2AN I Analog actual value signal, reference ground
15 PIST1AP PIST2AP I Analog actual value signal, max. range 0...10 V
I = Input, O = Output
The inputs are differential inputs with 40 kΩ input resistance.
The input voltage range is 0...+10 V.
The power supply output is provided with electronic short–circuit protection.
The power supply output is designed for a total current (4 sensors) of 200 mA.
Supply, pressure sensors with 26.5 V "2 % according to the external supply at
X431.
Notice
The external 26.5 V power supply voltage cannot be replaced by a 24 V
voltage.