5.9 Control module ”HLA module”
5-150
Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
S X121: Axis 1
S X122: Axis 2
Table 5-24 ConnectorsX121, X122;15–pin D–Sub socket connector
Pin X121 X122 Type
1)
Function
1 P24RV1 P24RV2 O +24 V switched
2 P24RV1 P24RV2 O +24 V switched
3 P24RV1 P24RV2 O +24 V switched
4 P24RV1 P24RV2 O +24 V switched
5 M M Electronics ground
6 VSET1N VSET2N O Analog setpoint output, reference ground
7 VSET1P VSET2P O Analog setpoint output +/–10 V
8 M M Electronics ground
9 M24EXT M24EXT O Ground, 24 V external
10 M24EXT M24EXT O Ground, 24 V external
11 M24EXT M24EXT O Ground, 24 V external
12 – – Not assigned
13 M M Electronics ground
14 VACT1N VACT2N I Analog valve actual value input, reference
ground
15 VACT1P VACT2P I Analog valve actual value input, +/–10 V
1) I = Input, O = Output
The analog valve actual value inputs are differential inputs with 100 kΩ input
resistance.
The load capability of the 24 V outputs, control value are
S for an ambient temperature 40 °C A2.0
S for an ambient temperature 55 °C 1.5 A
for the average current value for a load duty cycle 10 s duration
It is permissible to linearly interpolate between the temperature transition points.
The short–time load capability of the control valve outputs is 3.0 A (200 ms).
When overloaded, the fuse F1900 or F1901 on the HLA control module is des-
troyed.
The outputs 24 V switched for axes 1 and 2 are protected using a fine fuse
F1900 (axis 1) and F1901 (axis 2).
Value: 2.5 AF/250 V; 5x20 mm UL
Company: Wickmann–Werke GmbH
Annenstraße 113
58453 Witten
or
Postfach 2520
58415 Witten
Order No.: 19194
Control valve
Fuse