6
05.01
6.1 Function overview and settings
6-167
 Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
Note
Only in conjunction with module Order No.: 6SN114_–1__0_–0__1.
For motors with shaft heightst100: Utilized up to max. 60 k values.
Please observe the Planning Guide, Motors.
S1.4 ON overwrites the functions of S1.5 and S1.1.
This function is only available in conjunction with I/R modules
Order number: 6SN114_–1B_0_–0_A1
OFF: Standard setting, controlled infeed active
ON: Uncontrolled operation in the infeed direction V
DC
link
= V
supply
1.35
Notice:
When the I/R units are operated uncontrolled, they must be de–rated by approx.
75 %.
OFF: Square–wave current operation (the line supply is loaded with
a square–wave current)
ON: This function is only available in conjunction with I/R modules
Order number: 6SN114_–1B_0_–0_A1
Sinusoidal current operation (the line supply is loaded with sinusoidal
current)
Note
For sinusoidal supply, the total length of the power cables (motor feeder cable,
DC link cable) may not exceed 350m, and for squarewave, they may not
exceed 500m.
Switch S1.5
Switch S1.6