Line connection and line-side power components
3.10 Combination options, Line Modules with line reactors and line filters
Booksize Power Units
136 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Table 3- 30 Combination options, Basic Line Modules with line filters and line reactors
BLM type
combined
with:
Features that can be achieved
20
kW
40
kW
100
kW
Filter/reactor
DC link step
up factor or
rectified
value B6
Total cable length for radio interference suppression
according to EN 61800-3
Can be
operated on
an IT line
system
BLF
FE
line
reac-
tor
Cat. C2
shielded
in m
Cat. C3
shielded
in m
Cat. C4
shielded
in m
Cat. C4
unshielded
in m
x
1.35
-
-
630
850
Yes
x
-
350
1000
1500
Yes
1)
x
x
350
630
630
850
No
x x 350 630 1000 1500 No
1)
Remove connection bracket