Motor Modules Booksize
6.3 Motor Module with external air cooling
Booksize Power Units
410 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
without derating
kHz
4
Hz 0 … 550
3
Max. permissible heat sink tempera-
ture
° C 70 70 70 90
Default for 400 V line systems; undervoltage trip threshold can be reduced by up to 80 V and is adjusted to the parame-
terized rated voltage
2)
Rated power of a typical standard induction motor at 400 V 3 AC
Note
Disturbance of the 18 A Single Motor Module with 300% overload during operation on a
16 kW Line Module
The maximum output of a 16
kW Line Module is not sufficient for the operation of an 18 A
Single Motor Module with 300% overload.
Do NOT operate an 18 A Single Motor Module with a 16 kW Line Module with 300%
overload (i.e. only operate an 18 A Single Motor Module with a 16 kW Line Module, if the
maximum current is limited to 2 x I
rated
).
Use at least a 36 kW Active Line Module or Smart Line Module for operation with 300%
overload.
Double Motor Modules (300% overload)
Table 6- 31 Technical data Double Motor Modules Booksize (2 x 3 to 2 x 9 A) with 300% overload
Rated current (l
n
)
Base-load current (I
H
)
Intermittent duty current (I
s6
) 40 %
max
A
AC
A
A
AC
AC
2 x 2.6
2 x 3.5
2 x 4.3
2 x 6
2 x 7.7
2 x 10
V
AC
0 … 480
d rated
DC
Overvoltage trip
1)
V
DC
820 ± 2 %
DC