Line connection and line-side power components
3.4 Line supply connection via residual-current devices
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
53
3.4
Line supply connection via residual-current devices
Selectively tripping, AC/DC-sensitive residual-current devices (type B) can be used in
addition to the overcurrent protection devices.
Residual-current devices have to be installed if the power supply conditions in terms of short-
circuit power and loop impedance at the infeed point are not such that the installed
overcurrent protection devices will trip within the prescribed period if a fault occurs.
WARNING
Danger to life due to electric shock of fire when using unsuitable residual current devices
The inverter can cause a current to flow in the protective conductor.
This current can cause the residual current device (RCD) or residual current monitoring
(RCM) to incorrectly trip (nuisance trip). In the case of a fault (ground fault), the fault current
can contain a DC component, which prevents the RCD/RCM from tripping, with the risk of
subsequent electric shock or fire.
Use the protection and monitoring devices recommended in the documentation.
3.4.1
Residual-current operated circuit breakers (RCD)
Residual-current operated circuit breakers (RCD) can be used in addition to the overcurrent
protection devices provided. They are the preferred solution for operation on TT systems.
Note
Operation on residual
-current operated circuit breakers is currently only possible with Line
Modules up to and including 36
kW.
Conditions when using residual current protective devices:
Only use a delayed tripping, selective AC/DC-sensitive residual-current operated circuit
breaker, type B.
Ensure that the loop impedance is maintained corresponding to local installation
regulations.
Check the total length of the shielded power cables (motor cables incl. line supply
conductors from line filters to the connecting terminals of the Line Module) in the drive
line-up. The total length must be less than 350 m.
Only operate the system with the recommended line filters.