Line connection and line-side power components
3.4 Line supply connection via residual-current devices
Booksize Power Units
54 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
If you connect residual-current devices in series, then they must all have the same
characteristics.
Ensure that the switching elements (disconnector unit, contactors) for connecting and
disconnecting the drive system have max. 35 ms delay time between the closing/opening
of the individual main contacts.
Figure 3-3 Connection of a residual-current protective device
Recommendation
SIEMENS selectively switching AC/DC-sensitive residual-current circuit-breakers according
to EN 61009-1 of the 5SM series (e.g. 5SM3646-5 or 5SM3646-5+5SW3300 with an
auxiliary disconnector (1 NC contact / 1 NO contact) for a rated current of 63 A and rated
fault current of 0.3 A (see Catalog "BETA Modular Installation Devices - ET B1")).
Note
AC or pulse
-sensitive RCCBs are not suitable.