DC link components
8.3 Braking Module Booksize Compact
Booksize Power Units
516 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Table 8- 16 Duty cycles
A [s] 3 20 3 20 3 20
Configuration instructions
DC link capacitance
When configuring the drive line-up, please note that only one Braking Module Booksize
Compact may be used per complete 500 µF DC link capacitance.
Table 8- 17 Configuration examples
DC link capacitance in µF
Max. number of Braking Modules
900 1
9,800 19
In a multi-row or distributed drive line-up, the DC links are connected to each other via a DC
link cable. When using a Braking Module Booksize Compact in the drive line-up, this cable
must not be longer than 10 m. In all cases, the DC link cable must have low impedance and
a cross-section of at least 10 mm
2
.
During configuration of parallel operation for Braking Modules Booksize Compact,
dimensioning can only take 90% of the specified braking power into account. Only the peak
powers may be added without derating.
The following applies when connecting Braking Modules in parallel:
P
N total
= 0.9 x total P
N
of single devices
4 x P
N total
= 0.9 x sum (4 x P
N
) of single devices
P
max total
= total P
max
of single devices