Braking resistors
9
9.1
Description
A braking resistor is used to dissipate the excess DC link energy in generator operation. The
braking resistors can be connected to a Braking Module or directly to a 20 kW or 40 kW
Basic Line Module.
Resistors with and without a thermostatic switch are available with various rated powers. The
thermostatic switch monitors the braking resistors for overtemperature and issues a signal at
an isolated contact if the limit value is exceeded.
Table 9- 1 Assignment of braking resistors
Braking resistor
Braking Module
Booksize
Braking Module
Booksize Com-
pact
Basic Line Mod-
ule 20 kW
Basic Line Mod-
ule 40 kW
Braking resistors without a thermostatic switch
6SN1113-1AA00-
0DA0
Resistance: 17 Ω
P
N
: 0.3 kW
X X - -
6SL3100-1BE31-
0AA0
Resistance: 5.7 Ω
P
N
: 1.5 kW
X X - -
Braking resistors with a thermostatic switch
6SE7018-0ES87-
2DC0
Resistance: 80 Ω
P
N
: 1.25 kW
- X X X
6SE7021-6ES87-
2DC0
Resistance: 40 Ω
P
N
: 2.5 kW
- X X X
6SE7023-2ES87-
2DC0
Resistance: 20 Ω
P
N
: 5 kW
- X X X
6SE7028-0ES87-
2DC0
Resistance: 8 Ω
P
N
: 12.5 kW
- - - X