Line Modules Booksize
4.6 Active Line Modules Liquid Cooled
Booksize Power Units
220 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
:
1. Firstly, tighten the nuts by hand.
Tightening torque: 0.5 Nm
2. Then tighten the nuts in the specified sequence 1 to 4.
Tightening torque: 10 Nm
For installation, M6 threaded bolts and hexagon nuts/grub screws ISO 7436-M6x40-14 H,
property class 8.8 are recommended.
The coolant connections are located on the lower side of the components. All connection
elements can be accessed using an appropriate tool.
● Thread type of water connections: Pipe thread ISO 228 G ½ B.
Table 4- 39 Technical data for an Active Line Module Liquid Cooled
1)
Rated power S1 duty
Infeed power S6 duty (40 %)
Peak infeed power
kW (P
n
)
kW (P
S6
)
kW (P
max
)
120
145
175
Continuous regenerative power
kW
120
Line voltage
Line frequency
V
ACrms
Hz
3 AC 380 … 480 ±10 % (- 15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
2)
V
DC
V
DC
DC
510 … 720
820 ± 2 %
Rated input current:
at AC 400 V
Input current
at AC 380 V / AC 480 V
at AC 400 V; S6 duty (40 %)
at AC 400 V; peak current
A
AC
A
AC
A
AC
182
192 / 152
220
Rated DC link current:
for 600 V:
DC link current:
for 600 V DC; S6 duty (40 %)
for 600 V DC; peak current
A
DC
A
DC
200
244
Current carrying capacity
DC link busbars
A
DC
DC
200