Line connection and line-side power components
3.8 Line reactors
Booksize Power Units
98 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Table 3- 15 Technical data for HFD line reactors
rms
Power loss
1)
(see power
W 170 250 350 450 590
Weight kg 9 23 27 37 67
Degree of protection to
IP00 (no touch protection)
1)
Data for line operation
Damping resistor for HFD line reactors
3.8.4.1
Description
Using a damping resistor
In some systems, oscillations can be generated which place an impermissibly high strain on
the insulation systems of the motors and converters involved. Connecting a damping resistor
to the additional winding of the HFD line reactor is an effective means of damping just such
system oscillations. Use of the 800 W damping resistor is preferable.
Note
Recommendation
Use an Active Interface Module as line connection component for new plants and systems
equipped with Active Line Modules.