Motor Modules Booksize
6.3 Motor Module with external air cooling
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
411
Electronics current drawn
at 24 VDC
DC
Current carrying capacity
DC-link busbars
Reinforced DC-link busbars
A
DC
A
DC
100
150
2)
Based on I
n
(600 VDC; 4 kHz)
H
kW
2 x 1.6
2 x 2.7
2 x 4.8
(including electronics losses, see Power loss tables
W 97.6 132.6 187.6
without derating
kHz
4
3
Max. permissible heat sink temperature
kg 5.8 5.8 5.7
Default for 400 V line systems; undervoltage trip threshold can be reduced by up to 80 V and is adjusted to the parame-
terized rated voltage
2)
Rated power of a typical standard induction motor at 400 V 3 AC
Note
Disturbance of the 2 x 9 A Double Motor Module with 300% overload during operation on a
16 kW Line Module
The maximum output of a 16
kW Line Module is not sufficient for the operation of a 2 x 9 A
Double Motor Module with 300% overload.
Do NOT operate a 2 x 9 A Double Motor Module with a 16 kW Line Module with 300%
overload (i.e. only operate a 2 x 9 A Double Motor Module with a 16 kW Line Module, if
the maximum current is limited to 2 x I
rated
).
Use at least a 36 kW Active Line Module or Smart Line Module for operation with 300%
overload.