Line Modules Booksize
4.3 Active Line Modules with internal air cooling
Booksize Power Units
170 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Rated DC link current:
for 600 V:
DC link current:
for 600 V DC; S6 duty (40 %)
for 600 V DC; peak current
A
DC
A
DC
A
DC
134
176
218
200
244
292
Current carrying capacity
DC link busbars
A
DC
DC
200
200
Electronics current drawn
at 24 V DC
(including electronics losses, see
Power loss tables (Page 756))
W 1383.6 2243.2
Active Line Module
μF
2820
3995
Circuit breaker
(IEC 60947 and UL)
See Chapter Overcurrent protection using fuses and circuit breakers
Rated short-circuit current
SCCR
3)
kA 65 65
4)
See Chapter Combination options, Line Modules with line reactors
and line filters (Page 135)
Cooling method (internal air cooling)
3
Max. permissible heat sink tempera-
ture
° C 70 75
Rated voltage for rated data 3 AC 380 V
The specified power ratings apply to the line voltage range from 380 V to 480 V.
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
Module in the drive system.
4)