Line Modules Booksize
4.5 Active Line Modules with cold plate
Booksize Power Units
208 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
25-5AA3 +
Active
Interface
Module
(IEC 60947 and UL)
See Chapter Overcurrent protection using fuses and circuit breakers
(Page 51)
-
4)
kA 65 65 65 65 65 65
5)
See Chapter Combination options, Line Modules with line reactors and line
Max. permissible heat sink
temperature
° C 70 73 83 83 75 80
Derating must be applied due to the transfer of heat to the external heat sink. At a temperature of 40° C at the interface
to the power unit, 80% derating occurs for 6SL3136-7TE28-0AA. and 70 % for 6SL3136-7TE31-2AA.
The specified power ratings apply to the line voltage range from 380 V to 480 V.
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
Module in the drive system.
5)
Maximum total cable length = Σ motor cables, line feeder cable from line filter to the Line Module
0 kW and 120 kW Active Line Modules should ideally be designed with
kW Active Line Modules Liquid Cooled in order to avoid power derating.