Motor Modules Booksize
6.3 Motor Module with external air cooling
Booksize Power Units
404 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Max. permissible heat sink tempera-
ture
° C 70 70 73 82 85
Applies only to Article numbers with "." = 0 ... 3
Default for 400 V line systems; undervoltage trip threshold can be reduced by up to 80 V and is adjusted to the parame-
terized rated voltage
3)
Rated power of a typical standard induction motor at 400 V 3 AC.
Table 6- 28 Technical data Single Motor Modules Booksize (45 to 200 A)
Rated current (l
n
)
Base-load current (I
H
)
Intermittent duty current (I
s6
) 40 %
A
AC
A
A
AC
38
60
51
80
68
110
105
150
141
230
AC
0 … 0.717 x DC-link voltage
DC
Overvoltage trip
1)
V
DC
DC
820 ± 2 %
Electronics current drawn
DC
Current carrying capacity
DC-link busbars
A
DC
DC
200
200
200
200
200
2)
Based on I
n
(600 VDC; 4 kHz)
kW
24
32
46
71
107
(including electronics losses, see
Power loss tables (Page 756))
W 455.2 615.2 786 1270.4 2070.4
without derating
kHz
4
3
Max. permissible heat sink tempera-
ture
° C 85 90 88 73 80
(70 % derat-