Motor Modules Booksize
6.4 Motor Modules with cold plate
Booksize Power Units
434 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Table 6- 43 Technical data Single Motor Modules (45A to 200A)
Rated current (I
n
)
Base-load current (I
H
)
Intermittent duty current (I
S6
) 40%
max
A
AC
A
A
AC
AC
38
60
51
80
68
110
(105)
1)
105 (84)
1)
150 (120)
1)
(140)
1)
141 (99)
1)
230 (161)
1)
d rated
DC
(up to 2000 m above sea level)
V
DC
510 … 720
Overvoltage trip Undervoltage trip
2)
V
DC
820 ± 2 %
DC
Electronics current drawn
Current carrying capacity
DC-link busbars
A
DC
DC
200
3)
Based on I
n
(600 VDC; 4 kHz)
kW
24
32
46
71 (57)
1)
1)
107 (75)
1)
1)
(including electronics losses, see
Power loss tables (Page 756))
W 448 608 769.2 1270.4 2070.4
without derating
kHz
4
Max. permissible heat sink tempera-
ture
° C 80 73 83 75 79
(70 % derat-
above/below
in front of the component
mm
≥ 80
≥ 80
Derating must be applied due to the transfer of heat to the external heat sink. At a temperature of 40° C at the interface
to the power unit, 80% derating occurs for 6SL3126-1TE31-3AA. and 70 % for 6SL3126-1TE32-0AA.
Default for 400 V line systems; undervoltage trip threshold can be reduced by up to 80 V (exception: 132 A and 200 A
Motor Modules) and is adjusted to the parameterized rated voltage.
3)
Rated power of a typical standard induction motor at 400 V 3 AC