System overview
2.5 System data
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
47
Table 2- 2 Modules
Line Modules in the booksize format
Max. permissible supply voltage
Rated pulse frequency
(for Active Line Modules in booksize format only)
8 kHz
Motor Modules in the booksize format
Rated pulse frequency 4 kHz
At higher pulse frequencies the corresponding characteristic
for current derating must be taken into consideration
Table 2- 3 Degree of protection / protection class
IPXXB according to EN 60529, open type according to UL/CSA
Power circuits
I (with protective conductor connection)
safety extra-low voltage PELV/SELV
Table 2- 4 Environmental conditions
Chemically active substances
Class 1C2 according to EN 60721-3-1, in product packaging
1)
Klasse 2C2 gemäß EN 60721-3-2, in transport packaging
2)
Class 3C2 according to EN 60721-3-3
Biological environmental conditions
Class 1B1 according to EN 60721-3-1, in product packaging
1)
Class 2B1 according to EN 60721-3-2, in transport packaging
2)
Class 3B1 according to EN 60721-3-3
Climatic environmental conditions
Long-term storage Class 1K4 according to EN 60721-3-1, in product packaging
1)
Temperature: -25 … +55 °C
Transport Class 2K4 according to EN 0721-3-2, in product packaging
2)
Temperature: -40 … +70 °C
Operation Class 3K3 according to EN 60721-3-3 with increased ruggedness with respect to
relative humidity
Temperature: 0 ... +40 °C without derating
> 40 ... +55 °C with reduction of the output current by 2.67 % pro °C
Relative humidity: 5 … 95 % no condensation (better than Class 3K3)
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water,
splashing water and water jets are not permitted
Mechanical environmental conditions
Class 1M2 according to EN 60721-3-1, in product packaging
1)
Class 2M3 according to EN 60721-3-2, in transport packaging
2)
Class 3M1 according to EN 60721-3-3
Vibration test in operation
According to IEC 60068-2-6 test Fc (sinusoidal)