Accessories
11.1 Shield connecting plates for power supply and motor cables
Booksize Power Units
618 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Example 2: 200 mm wide component with internal air cooling
Required tools:
Torx screwdriver T25 for protective conductor connection (Torx slot)
(Torque) wrench M8 for power cables
Flat-bladed screwdriver for hose clamp
Table 11- 9 Connecting power cables for a 200 mm wide component using internal air cooling as an example
1. Release and open the cover of the
terminal strip.
2. Remove the M8 nuts. 3. Attach the protective conductor and
the power cable.
Tightening torque: 13 Nm
4. Adapt a restrictor collar (using a
suitable tool) for the touch protection.
5. Push on the reduction collar. 6. Tighten the hose clamp at the shield
connecting plate.

Table of Contents