Line connection and line-side power components
3.7 Line filters
Booksize Power Units
70 Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Damage caused by overheating as a result of an inadmissible mounting position
If the component is not operated in a vertical position with the line supply terminals at the
bottom, then the component can be damaged.
• Only operate the components in a vertical position with the line terminals at the bottom.
Table 3- 7 Line and load connection, Wideband Line Filter for Active Line Modules
Line supply connection
Screw terminals:
10 mm
2
3 pole
M4 / 1.5 …
1.8 Nm
Screw terminals
50 mm
2
, 3 pole
M6 / 6 … 8 Nm
Screw terminals
95 mm
2
, 3-pole
M8 / 15 … 20 Nm
Connection lugs
d = 11 mm
M10 / 25 Nm
No
touch protection
(IP00 acc. to
IEC 60529); touch
protection must be
provided on the
plant/system side.
Load connection
U, V, W
PE connection
1)
Terminal studs
Terminal studs
Terminal studs
1)
For ring cable lugs without insulation (Page 732)