133: Access method not dened.
200: Below the v
alid values.
201: Above the valid values.
202: Cannot be accessed from the Basic Operator Panel (BOP).
203: Cannot be read from the Basic Operator Panel (BOP).
204: Write access not permitted.
Remedy: - Correct the parameterization in the commissioning tool and download the project again.
- Enter the cor
rect value in the specied parameter.
- Identify the parameter that restricts the limits of the specied parameter.
A01100 CU: Memory card withdrawn
Message class: General drive fault (19)
Message value: -
Component: Control Unit (CU)
Response: NONE
Acknowledgment: NONE
Cause: The memory card (non-volatile memory) was withdrawn during operation.
No
tice:
It is not permis
sible for the memory card to be withdrawn or inserted under voltage.
Remedy: - Switch o the driv
e system.
- Re-insert the memory card that was withdrawn - This card must match the drive system.
- Switch on the drive system again.
F01105 CU: Insucient memory
Messag
e class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: %1
Component: Control Unit (CU)
Response: OFF1
Acknowledgment: POWER ON
Cause: The functionality on this Control Unit is too extensive (e.g. too many drives, functions, data sets, Technology Extensions,
bloc
ks, e
tc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - Change the conguration on this Contr
ol Unit, e.g.
-- Use fewer axes
-- Reduce the number of congurable functions
-- Use fewer data sets
-- Reduce Technology Extensions and blocks
- Use an additional Control Unit.
F01107 CU: Save to memory card unsuccessful
Message class: Hardware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: NONE
Acknowledgment: IMMEDIATELY