Cause: A data save in the non-volatile memory was not able to be successfully carried out.
- Non-volatile memory is def
ective.
- Insu󹪟cient space in the non-volatile memory.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - Try to save again.
- Replace the memory car
d or Control Unit.
F01110 CU: More than one SINAMICS G on one Control Unit
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: More than one SINAMICS G type power unit is being operated from the Control Unit.
F
ault value (r0949, int
erpret decimal):
Number of the second drive with a SINAMICS G type power unit.
Remedy: Only one SINAMICS G drive type is permitted.
F01111 CU: Mixed operation of drive units illegal
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: Illegal operation of various drive units on one Control Unit:
- SIN
AMICS S tog
ether with SINAMICS G
- SINAMICS S together with SINAMICS S Value or Combi
Fault value (r0949, interpret decimal):
Number of the 󹪝rst drive object with a di󹪜erent power unit type.
Remedy: Only power units of one particular drive type may be operated with one Control Unit.
F01122 Frequency at the measuring probe input too high
Message class: Application/technological function faulted (17)
Message value: %1
Component: None
Response: OFF1
Acknowledgment: IMMEDIATELY
Cause: The frequency of the pulses at the measuring probe input is too high.
F
ault value (r0949, int
erpret decimal):
1: DI/DO 9 (X122.8)
2: DI/DO 10 (X122.10)
4: DI/DO 11 (X122.11)
8: DI/DO 13 (X132.8)
16: DI/DO 14 (X132.10)
32: DI/DO 15 (X132.11)
64: DI/DO 8 (X122.7)
128: DI/DO 12 (X132.7)
Remedy: Reduce the frequency of the pulses at the measuring probe input.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
452 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS SIMOTICS S200 PROFINET and is the answer not in the manual?

Siemens SINAMICS SIMOTICS S200 PROFINET Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS SIMOTICS S200 PROFINET
CategoryServo Drives
LanguageEnglish

Related product manuals