F01152 CU: Invalid constellation of drive object types
Message class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: POWER ON
Cause: It is not possible to simultaneously operate drive object types SERVO, VECTOR and HLA.
A maximum of 2 of t
hese driv
e object types can be operated on a Control Unit.
Remedy: - Switch o the unit.
- Restr
ict the use of drive object types SERVO, VECTOR, HLA to a maximum of 2.
- Re-commission the unit.
F01200 CU: Time slice management internal software error
Message class: Hardware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: A time slice management error has occurred.
It is pos
sible that t
he sampling times have been inadmissibly set.
Fault value (r0949, interpret hexadecimal):
998:
Too many time slices occupied by technology functions (e.g. DCC).
999:
Too many time slices occupied by the basic system. Too many dierent sampling times may have been set.
Additional values:
Only for internal Siemens troubleshooting.
Remedy: - Contact Technical Support.
F01205 CU: Time slice overo
w
Message class: Hardware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: OFF2
Acknowledgment: POWER ON
Cause: Insucient pr
ocessing time is a
vailable for the existing topology.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - Reduce the number of drives.
F01250 EEPROM incorrect read-only data
Message class: Hardware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: NONE
Acknowledgment: POWER ON
Cause: Error when reading the read-only data of the EEPROM in the converter.
F
ault value (r0949, int
erpret decimal):
Only for internal Siemens troubleshooting.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
454 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB