F01325 Topology: Component number not included in target topology
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: Component number: %1
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The component referenced in a data set (e.g. PDS, MDS or EDS) is not contained in the target topology.
F
ault value (r0949, int
erpret decimal)
Remedy: Establish consistency between the topology and data set con󹪝guration.
A01330 Topology: Quick commissioning not possible
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: Fault cause: %1, supplementary information: %2, preliminary component number: %3
Component: None
Response: NONE
Acknowledgment: NONE
Cause: Unable to carry out a quick commissioning. The existing actual topology does not ful󹪝ll t
he req
uirements.
Remedy: - Check the motor connection.
- Carry out a POWER ON (switc
h-o󹪜/switch-on).
F01356 Topology: There is a defective component
Message class: Hardware/software error (1)
Message value: Fault cause: %1, Component number: %2, Connection number: %3
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The actual topology indicates at least one defective component.
No
te:
Pulse enable is withdrawn and prevented.
Remedy: Replace the defective component and restart the system.
F01380 Topology: Actual topology EEPROM defective
Message class: Hardware/software error (1)
Message value: Preliminary component number: %1
Component: None
Response: NONE
Acknowledgment: POWER ON
Cause: When detecting the actual topology, a component with a defective EEPROM was detected.
F
ault value (r0949, int
erpret hexadecimal):
bbbbaaaa hex:
bbbb = reserved
aaaa = preliminary component number of the defective components
Remedy: Output the fault value and remove the defected component.
A01382 Topology: Sensor Module incorrectly inserted
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: Component: %1, to %2, %3, connection: %4
Component: None
Response: NONE
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
458 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS SIMOTICS S200 PROFINET and is the answer not in the manual?

Siemens SINAMICS SIMOTICS S200 PROFINET Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS SIMOTICS S200 PROFINET
CategoryServo Drives
LanguageEnglish

Related product manuals