Message value: Info 1: %1, Info 2: %2
Component: None
Response: NONE
Acknowledgment: NONE
Cause: A controller attempts to establish a connection to the drive, and as a consequence exceeds the permitted number of
PR
OFINET connections.
The alarm is automaticall
y withdrawn after approx. 30 seconds.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info 1 = 0: number of RT connections exceeded
Info 1 > 0: number of IRT connections exceeded
Info 2: permitted number of connections
Remedy: Check the con󹪝guration of the PR
OFINET controllers.
A01989 PN: internal cyclic data transfer error
Message class: Communication error to the higher-level control system (9)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The cyclic actual values and/or setpoints were not transferred within the speci󹪝ed times.
Alarm value (r2124, int
erpre
t hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: Correctly set T_io_input or T_io_output.
A02000 Function generator: Start not possible
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The function generator has already been started.
Remedy: Stop the function generator and restart again if necessary.
No
te:
The alarm is r
eset as follows:
- Remove the cause of this alarm.
- Restart the function generator.
A02006 Function generator: No drive speci󹪝ed for connection
Messag
e class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: No drive speci󹪝ed f
or connection was
speci󹪝ed.
Remedy: At least one drive to be connected must be speci󹪝ed.
Note:
The alarm is r
eset as follows:
- Remove the cause of this alarm.
- Restart the function generator.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 491