A02010 Function generator: Speed setpoint from the drive is not zero
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The speed setpoint of a drive selected for connection is greater than the value for the standstill detection set using p1226.
Remedy: For all of the drives speci󹪝ed f
or connection, set t
he speed setpoints to zero.
Note:
The alarm is reset as follows:
- Remove the cause of this alarm.
- Restart the function generator.
A02020 Function generator: Parameter cannot be changed
Message class: Error in the parameterization / con󹪝gur
ation / commis
sioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: This parameter setting cannot be changed when the function generator is active.
Remedy: - Stop the function generator before parameterizing.
- P
ossibl
y start the function generator.
Note:
The alarm is reset as follows:
- Remove the cause of this alarm.
- Restart the function generator.
A02026 Function generator: Pulse width too high
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The selected pulse width is too high.
The pulse widt
h must be les
s than the period duration.
Remedy: Reduce pulse width.
Note:
The alarm is r
eset as follows:
- Remove the cause of this alarm.
- Restart the function generator.
A02030 Function generator: Physical address equals zero
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The speci󹪝ed ph
ysical addr
ess is zero.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
492 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB