Cause: The "master control by PLC" signal was missing in operation.
- The higher-lev
el control has withdrawn the "master control by PLC" signal.
- Data transfer via the 󹪝eldbus (controller/drive) was interrupted.
Remedy: - Check the "master control by PLC" signal and, if required, switch in.
- Check data tr
ansfer via the 󹪝eldbus (controller/drive).
Note:
If the drive should continue to operate after withdrawing "master control by PLC", then the fault response must be
parameterized to NONE or the message type should be parameterized as alarm.
F07300 Drive: Line contactor feedback signal missing
Message class: Auxiliary unit faulted (20)
Message value: -
Component: None
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: - The line contactor was not able to be closed within the time in p0861.
- The line cont
act
or w
as not able to be opened within the time in p0861.
- The line contactor dropped out during operation
- The line contactor has closed although the drive converter is switched o󹪜.
Remedy: - Check the setting of p0860.
- Check the f
eedback circuit from the line contactor.
- Increase the monitoring time in p0861.
A07350 Drive: Measuring probe parameterized to a digital output
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The measuring probe is connected to a bidirectional digital input/output and the terminal is set as output.
Alarm v
alue (r2124, interpr
et decimal):
8: DI/DO 8 (X122.9/X132.1)
9: DI/DO 9 (X122.10/X132.2)
10: DI/DO 10 (X122.12/X132.3)
11: DI/DO 11 (X122.13/X132.4)
12: DI/DO 12 (X132.9)
13: DI/DO 13 (X132.10)
14: DI/DO 14 (X132.12)
15: DI/DO 15 (X132.13)
Regarding the terminal designation:
The 󹪝rst designation is valid for CU320, the second for CU305.
Remedy: - Deselect measuring probe (p0488, p0489).
F07410 Drive: Current controller output limited
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: OFF2
Acknowledgment: IMMEDIATELY
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 509