Response: NONE
Acknowledgment: NONE
Cause: A traversing block selected via binector input c2625 ... c2629 was started via binary signal c2631 = 0/1 edge "Activate
tr
aversing task".
- The number of the started traversing block is not contained in p2616[0...n].
- The started traversing block is suppressed.
Alarm value (r2124, interpret decimal):
Number of the selected traversing block that is also not available.
Remedy: - Correct the traversing program.
- Select an available tr
aversing block number.
A07463 EPOS: External block change not requested in the traversing block
Message class: Application/technological function faulted (17)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
Cause: For a traversing block with the block change enable CONTINUE_EXTERNAL_ALARM, the external block change was not
r
eq
ues
ted.
Alarm value (r2124, interpret decimal):
Number of the traversing block.
Remedy: Resolve the reason why the signal edge at the measuring probe is missing.
F07464 EPOS: Traversing block is inconsistent
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: %1
Component: None
Response: OFF1
Acknowledgment: IMMEDIATELY
Cause: The traversing block does not contain valid information.
Alarm v
alue (r2124, interpr
et decimal):
Number of the traversing block with invalid information.
Remedy: Check the traversing block and where relevant, take into consideration alarms that are present.
A07465 EPOS: Traversing block does not have a subsequent block
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
Cause: There is no subsequent block in the traversing block.
Alarm v
alue (r2124, interpr
et decimal):
Number of the traversing block with the missing subsequent block.
Remedy: - Parameterize this traversing block with the block change enable END.
- Par
ameterize additional traversing blocks with a higher block number and for the last block, using the block change enable
END.
A07466 EPOS: Traversing block number assigned a multiple number of times
Message class: Error in the parameterization / con󹪝gur
ation / commis
sioning pr
ocedure (18)
Message value: %1
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 517