F07484 EPOS: Fixed stop outside the monitoring window
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: OFF3
Acknowledgment: IMMEDIATELY
Cause: In the "󹪝x
ed st
op reached" state, the axis has moved outside the de󹪝ned monitoring window (p2635).
Remedy: - Check the monitoring window (p2635).
- Check the mec
hanical system.
F07485 EPOS: Fixed stop not reached
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: OFF1
Acknowledgment: IMMEDIATELY
Cause: In a traversing block with the task FIXED STOP, the end position was reached without detecting a 󹪝x
ed st
op.
Remedy: - Check the traversing block and locate the target position further into the workpiece.
- If requir
ed, reduce the maximum following error window to detect the 󹪝xed stop (p2634).
A07486 EPOS: Intermediate stop missing
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: In operating mode "traversing blocks" or "direct setpoint input/MDI", at the start of motion, c2640 is set to an intermediate
s
top, i.e. to a 0 signal.
Remedy: Set c2640 to "No intermediate stop" (1 signal) and restart motion.
See also: c2640 (EPOS intermediate s
top (0 signal))
A07487 EPOS: Reject traversing task missing
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: In the modes "Traversing blocks" or "Direct setpoint input/MDI" at the start of motion, the binary signal sink "Do not reject
tr
av
ersing task/reject traversing task" (c2641) does not have a 1 signal.
Remedy: Connect a 1 signal to the binary signal sink "Do not reject traversing task/reject traversing task" (c2641) and restart motion.
See also: c2641 (EPOS reject tra
versing task (0 signal))
F07488 EPOS: Relative positioning not possible
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: OFF1
Acknowledgment: IMMEDIATELY
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
522 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB