Remedy: - Correct the target position.
- Change the neg
ative software limit switch (c2578, p2580).
See also: c2578 (EPOS negative software limit switch), p2580 (EPOS negative software limit switch), c2582 (EPOS software
limit switch activation)
A07480 EPOS: Positive software limit switch reached
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The axis is at the position of the positive software limit switch. An active traversing block was interrupted.
Remedy: - Correct the target position.
- Chang
e the positiv
e software limit switch (c2579, p2581).
See also: c2579 (EPOS positive software limit switch), p2581 (EPOS positive software limit switch), c2582 (EPOS software
limit switch activation)
F07481 EPOS: Axis position < negative software limit switch
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: OFF1
Acknowledgment: IMMEDIATELY
Cause: The actual position of the axis is less than the position of the negative software limit switch.
Remedy: - Correct the target position.
- Chang
e the neg
ative software limit switch (c2578, p2580).
See also: c2578 (EPOS negative software limit switch), p2580 (EPOS negative software limit switch), c2582 (EPOS software
limit switch activation)
F07482 EPOS: Axis position > positive software limit switch
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: OFF1
Acknowledgment: IMMEDIATELY
Cause: The actual position of the axis is greater than the position of the positive software limit switch.
Remedy: - Correct the target position.
- Chang
e the positiv
e software limit switch (c2579, p2581).
See also: c2579 (EPOS positive software limit switch), p2581 (EPOS positive software limit switch), c2582 (EPOS software
limit switch activation)
A07483 EPOS: Travel to 󹪝xed s
top clamping torque not reached
Message class: Application/technological function faulted (17)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The 󹪝x
ed stop in the traversing block was reached without the clamping torque/clamping force having been achieved.
R
emedy: - Check the torque limits (p1520, p1521).
System messages
12.3Faults and alarms