Remedy: - Check the power supply.
- Replace Terminal Board 30.
A08560
IE: Syntax error in con󹪝guration 󹪝le
Mes
sage class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: A syntax error has been detected in the con󹪝gur
ation 󹪝le f
or the Industrial Ethernet interface (X127). The saved
con󹪝guration 󹪝le has not been loaded.
Note:
IE: Industrial Ethernet
Remedy: Reinitialize the station using the "Edit Ethernet node" screen form (e.g. with Startdrive commissioning tool).
A08561 IE: Consistency error a󹪜ecting adjustable par
ameters
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
Cause: A consistency error was detected when activating the con󹪝gur
ation for t
he Industrial Ethernet interface (X127).
Alarm value (r2124, interpret decimal):
0: General consistency error
1: Error in the IP con󹪝guration (IP address, subnet mask or standard gateway).
2: Error in the station names.
5: Standard gateway is also set at the PROFINET interface.
6: The station name is also set at the PROFINET interface.
7: The IP address is located in the same subnet as the IP address of the PROFINET interface.
Note:
For alarm value = 0, 1, 2, 5, 7 the following applies: the con󹪝guration was not changed.
For alarm value = 6 the following applies: The new con󹪝guration was however activated.
IE: Industrial Ethernet
Remedy: Reinitialize the station using the "Edit Ethernet node" screen form (e.g. with Startdrive commissioning tool).
A08562 PROFINET: Syntax error in con󹪝guration 󹪝le
Mes
sage class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: A syntax error has been detected in the con󹪝gur
ation 󹪝le f
or the PROFINET interface (X150). The saved con󹪝guration 󹪝le
has not been loaded.
Remedy: Reinitialize the station using the "Edit Ethernet node" screen form (e.g. with Startdrive commissioning tool).
A08563 PROFINET: Consistency error a󹪜ecting adjustable par
ameters
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: %1
Component: None
Response: NONE