F07955 Drive: Motor has been changed
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: Motor
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The code number of the actual self-identifying motor does not match the saved number.
If a
vailable:
The code number
s of the bearings, gearbox and brake do not match the saved numbers.
Remedy: Connect the original motor and switch on the converter again (POWER ON) - or restore the factory settings.
Note:
The dat
a for bearings, gearbox and brake are reloaded.
F07956 Drive: Motor code does not match the list (catalog) motor
Message class: Error in the parameterization / con󹪝gur
ation / commis
sioning pr
ocedure (18)
Message value: %1
Component: Motor
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The motor code of the connected self-identifying motor does not match the possible list motor types (see selection in
p0300).
It is pos
sible that t
his 󹪝rmware version does not support the connected motor.
Fault value (r0949, interpret decimal):
Motor code of the connected motor.
Note:
The 󹪝rst three digits of the motor code generally correspond to the list motor type.
Remedy: Use a self-identifying motor with the matching motor code.
F08000 TB: +/-15 V power supply faulted
Message class: Supply voltage fault (undervoltage) (3)
Message value: %1
Component: Controller Extension (CX)
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: Terminal Board 30 detects an incorrect internal power supply voltage.
F
ault value (r0949, int
erpret decimal):
0: Error when testing the monitoring circuit.
1: Fault in normal operation.
Remedy: - Replace Terminal Board 30.
- Replace Control Unit.
F08010 TB: Analog-digital converter
Message class: Hardware/software error (1)
Message value: -
Component: Controller Extension (CX)
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The analog/digital converter on Terminal Board 30 has not supplied any converted data.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 535