Remedy: - If required, start an additional period.
- Deactivate functions r
equiring a license.
- Appropriately license the drive unit.
Note:
A license that is not adequate will only become evident after the next time the system runs up.
A13032 Trial License last period activated
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: Control Unit (CU)
Response: NONE
Acknowledgment: NONE
Cause: The "Trial License" function was activated. The last of the available periods is expiring.
Remedy: Not necessary.
The alarm is aut
omatically wit
hdrawn after the last period has expired.
A13033 Trial License last period expired
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: -
Component: Control Unit (CU)
Response: NONE
Acknowledgment: NONE
Cause: The last period of the "Trial License" function has expired. No additional periods available.
Remedy: - Deactivate functions requiring a license.
- Appr
opriat
ely license the drive unit.
Note:
A license that is not adequate will only become evident after the next time the system runs up.
F30001 Drive: overcurrent
Message class: Power electronics faulted (5)
Message value: Fault cause: %1 bin
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The drive has detected an overcurrent condition.
- Closed-loop contr
ol is incorr
ectly parameterized.
- Motor has a short-circuit or fault to ground (frame).
- The rated motor current is signi󹪝cantly higher than that of the drive.
- Infeed: High discharge and post-charging currents for line voltage dip.
- Infeed: High post-charging currents for overload when motoring and DC link voltage dip.
- Infeed: Short-circuit currents at switch-on as there is no line reactor.
- Power cables are not correctly connected.
- The power cables exceed the maximum permissible length.
- Defective drive.
- Line phase interrupted.
Fault value (r0949, interpret bit-serial):
Bit 0: Phase U.
Bit 1: Phase V.
Bit 2: Phase W.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
540 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB