Cause: Hardware current limit for phase U responded. The pulsing in this phase is inhibited for one pulse period.
- Closed-loop control is incorr
ectly parameterized.
- Fault in the motor or in the power cables.
- The power cables exceed the maximum permissible length.
- Motor load too high
- Power unit defective.
Remedy: - Check the motor data.
- Check the mo
tor circuit con󹪝guration (star/delta).
- Check the motor load.
- Check the power cable connections.
- Check the power cables for short-circuit or ground fault.
- Check the length of the power cables.
A30032 Power unit: Hardware current limiting in phase V
Message class: Power electronics faulted (5)
Message value: -
Component: Power Unit
Response: NONE
Acknowledgment: NONE
Cause: Hardware current limit for phase V responded. The pulsing in this phase is inhibited for one pulse period.
- Closed-loop contr
ol is incor
r
ectly parameterized.
- Fault in the motor or in the power cables.
- The power cables exceed the maximum permissible length.
- Motor load too high
- Power unit defective.
Remedy: - Check the motor data.
- Check the mo
tor circuit con󹪝guration (star/delta).
- Check the motor load.
- Check the power cable connections.
- Check the power cables for short-circuit or ground fault.
- Check the length of the power cables.
A30033 Power unit: Hardware current limiting in phase W
Message class: Power electronics faulted (5)
Message value: -
Component: Power Unit
Response: NONE
Acknowledgment: NONE
Cause: Hardware current limit for phase W responded. The pulsing in this phase is inhibited for one pulse period.
- Closed-loop contr
ol is incorr
ectly parameterized.
- Fault in the motor or in the power cables.
- The power cables exceed the maximum permissible length.
- Motor load too high
- Power unit defective.
Remedy: - Check the motor data.
- Check the mo
tor circuit con󹪝guration (star/delta).
- Check the motor load.
- Check the power cable connections.
- Check the power cables for short-circuit or ground fault.
- Check the length of the power cables.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
550 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB