Cause: Communications error with an EEPROM or an analog/digital converter.
Fault value (r0949, int
erpret hexadecimal):
80000000 hex:
- Internal software error.
00000001 hex ... 0000FFFF hex:
- Module fault.
Remedy: For fault value = 80000000 hex:
- Upgr
ade rmware to later version.
For fault value = 00000001 hex ... 0000FFFF hex:
- Replace the module.
F30907 Power unit: FPGA conguration unsuccessful
Mes
sage class: Hardware/software error (1)
Message value: -
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: During initialization within the power unit, an internal software error has occurred.
Remedy: - If required, upgrade the rm
war
e in the power unit.
- Replace power unit.
- Contact Technical Support.
A30919 Power unit: Temperature monitoring failed
Message class: Overtemperature of the electronic components (6)
Message value: %1
Component: Power Unit
Response: NONE
Acknowledgment: NONE
Cause: The temperature monitoring in the power unit has failed.
F
ault-free oper
ation of the drive system is no longer guaranteed.
Alarm value (r2124, interpret binary):
Bit 0: Sensor 1 for the internal temperature can no longer be evaluated.
Bit 1: Sensor 2 for the internal temperature can no longer be evaluated.
Remedy: Replace the power unit immediately.
F30950 Power unit: Internal software error
Message class: Hardware/software error (1)
Message value: %1
Component: Power Unit
Response: OFF2
Acknowledgment: POWER ON
Cause: An internal software error has occurred.
F
ault value (r0949, int
erpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy: - If necessary, upgrade the rmwar
e in the power unit to a later version.
- Contact Technical Support.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 575