Appendix
A
A.1 UL Markings
Descr
iption
Con
verter variant of 1 AC/3 AC 200 V ... 240 V
For US/Canadian installations (UL/cUL): The products are cULus-listed under File E355661.
• Suitable for use in a circuit that cannot provide more than 100kArms (symmetrical), max.
240î™ V.
Note: The maximum permissible short-circuit current for 200 V variants with Type E
Combination Motor Controllers is 65î™ kA.
• Protection of the branch circuit for individual drives must be guaranteed using Class J fuses
in accordance with the technical data.
For other protection equipment and SCCRs (Short Circuit Current Rating) for individual
drives, see:
Protective Devices for SINAMICS S200 Product Line (
https://
support.industry.siemens.com/cs/ww/en/ps/29596/man)
• This device mus
t be installed in an enclosure that provides an environment with degree of
pollutionî™ 2 (controlled).
• Maximum rated temperature 45°C.
• The device provides overtemperature and overload protection.
• Use copper wires with a permissible temperature of 75 °C for all power cables. You can also
use cables with a higher rated temperature value. It is not permissible to reduce the
conductor cross-section.
Converter variant of 3 AC 380 V ... 480 V
For US/Canadian installations (UL/cUL): The products are cULus-listed under File E355661.
• Suitable for use in a circuit that cannot provide more than 65kArms (symmetrical), max.
480î™ V.
• Protection of the branch circuit for individual drives must be guaranteed using Class J fuses
in accordance with the technical data.
• For other protection equipment and SCCRs (Short Circuit Current Rating) for individual
drives, see:
Protective Devices for SINAMICS S200 Product Line (
https://
support.industry.siemens.com/cs/ww/en/ps/29596/man)
• This device mus
t be installed in an enclosure that provides an environment with degree of
pollutionî™ 2 (controlled).
• Maximum rated temperature 45°C. Maximum height 4000m.
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 687

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS SIMOTICS S200 PROFINET and is the answer not in the manual?

Siemens SINAMICS SIMOTICS S200 PROFINET Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS SIMOTICS S200 PROFINET
CategoryServo Drives
LanguageEnglish

Related product manuals