Dependency: See also: r8961
Note
For value = 10:
If t
he connection remains in this state, then when using PROFINET IRT the following can apply:
- Topology error (incorrect port assignment).
- Synchronization missing.
r8937[0...5] PN cyclic connection diagnostics
Data type: Unsigned32 Visible in: Ext
ended display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device congur
ation or driv
e applications
Parameter group:
Unit: -
Description: Display to diagnose the cyclic PROFINET connection.
Index: [0] = Number of cyclic connections
[1] = Number of send subslots of all connections
[2] = N
umber of send net data (bytes) of all connections
[3] = Number of receive subslots of all connections
[4] = Number of receive net data (bytes) of all connections
[5] = Connection type (RT, IRT)
Note
The paramet
er is active when the "PROFINET Device" protocol is selected.
For index [5]:
Bit 0 = 1: there is at least one RT connection.
Bit 1 = 1: there is an IRT connection.
r8961[0...3] PN controller IP address
Data type: Unsigned8 Visible in: Ext
ended display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device congur
ation or driv
e applications
Parameter group: Conguration
Unit: -
Description: Displays the IP address of the PROFINET controller.
c8995[0...3] Ethernet X127 enable
Data type: Unsigned8 Visible in: Ext
ended display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device congur
ation or driv
e applications
Parameter group: Conguration
Unit: -
Description: Signal to enable the Ethernet interface X127 for applications.
Index: [0] = Secure S7 Protocol Startdrive
[1] = Web serv
er HTTPS
[2] = S7 protocol PCS7
[3] = Web server HTTP
Appendix
A.3Parameters
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2