E: Environmental Specifications
C10 HD Installation Manual Section 6: Appendices | Page 6-17
Temperature Operating: 5 to 30 Deg. C
Non-operating: -20 to 50 Deg. C
M
ax. Gradient: 15 Deg. C/Hour
Relative Humidity Operating: 20 to 80 %
Non-operating: 5 to 90 %
Max. wet bulb: 29 Deg. C (non-condensing)
Vibration Operating: < 0.2 G (3 - 100Hz.)
Non-operating, power off: < 0.4 G (3 - 100Hz.)
Shock Operating: < 2 G (10mSec. Max.)
Non-operating: < 10 G (10mSec. Max.)
Altitude Operating: 0 to 3000 m
(Above sea level) Non-operating: 0 to 12000 m
 ($!  & %"&!
!&% $&  &! %&&   $ ! &!  
Any item of electronic equipment can be affected by electrostatic discharge. It is considered good practice to avoid
using fully insulating floor coverings in technical areas.
Air conditioning will usually be required. Note however, that a cool and dry atmosphere can significantly increase the
likelihood of a build-up of static charge. It is recommended that air conditioning systems are designed such that the
relative humidity does not fall below 30% during periods of operation.