Table 51: Analogue input 1 settings
Index Parameter Min Max Unit Default ID Description
P3.5.2.1.1 AI1 Signal Selection
AnIN
SlotA.1
377
Connect the AI1 signal
to the analogue input
of your choice with this
parameter.
Programmable. See
9.7.1 Programming of
digital and analogue
inputs.
P3.5.2.1.2
AI1 Signal Filter
Time
0.00 300.00 s 0.1 * 378
The filter time for the
analogue input.
P3.5.2.1.3
AI1 Signal Range 0 1 0 * 379
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
P3.5.2.1.4
AI1 Custom. Min -160.00 160.00 % 0.00 * 380
The custom range
minimum setting, 20%
= 4-20 mA/2-10 V
P3.5.2.1.5
AI1 Custom. Max -160.00 160.00 % 100.00 * 381
The custom range
maximum setting.
P3.5.2.1.6
AI1 Signal Inversion 0 1 0 * 387
0 = Normal
1 = Signal inverted
Table 52: Analogue input 2 settings
Index Parameter Min Max Unit Default ID Description
P3.5.2.2.1 AI2 Signal Selection
AnIN
SlotA.2
388
See P3.5.2.1.1.
P3.5.2.2.2
AI2 Signal Filter
Time
0.00 300.00 s 0.1 * 389
See P3.5.2.1.2.
P3.5.2.2.3 AI2 Signal Range 0 1 1 * 390 See P3.5.2.1.3.
P3.5.2.2.4 AI2 Custom. Min -160.00 160.00 % 0.00 * 391 See P3.5.2.1.4.
P3.5.2.2.5 AI2 Custom. Max -160.00 160.00 % 100.00 * 392 See P3.5.2.1.5.
P3.5.2.2.6 AI2 Signal Inversion 0 1 0 * 398 See P3.5.2.1.6.