Table 89: Soft fill settings
Index Parameter Min Max Unit Default ID Description
P3.13.8.1
Enable Soft Fill 0 1 0 1094
0 = Disabled
1 = Enabled
P3.13.8.2
Soft Fill Frequency 0.00 50.00 Hz 20.00 1055
The drive accelerates
to this frequency
before it starts to
control. After this, the
drive goes to normal
PID control mode.
P3.13.8.3
Soft Fill Level Varies Varies Varies 0.0000 1095
The drive operates at
the PID start frequency
until the feedback
reaches this value.
Then the controller
starts to control.
P3.13.8.4
Soft Fill Timeout 0 30000 s 0 1096
If the target value is
not reached in this
time, a fault or alarm
shows.
0 = No timeout
NOTE!
If you set the value to
be 0, no fault shows.
P3.13.8.5
PID Soft Fill Timeout
Response
0 3 2 738
0 = No action
1 = Alarm
2 = Fault (Stop
according to stop
mode)
3 = Fault (Stop by
coasting)
PARAMETERS MENU VACON · 183