Table 88: Pressure loss compensation parameters
Index Parameter Min Max Unit Default ID Description
P3.13.7.1
Enable Setpoint 1 0 1 0 1189
Enables pressure loss
compensation for the
setpoint 1.
0 = Disabled
1 = Enabled
P3.13.7.2
Setpoint 1 Max
Compensation
Varies Varies Varies Varies 1190
The value that is added
proportionally to the
frequency. Setpoint
compensation = max
compensation *
(FreqOut-MinFreq)/
(MaxFreq-MinFreq).
P3.13.7.3 Enable Setpoint 2 0 1 0 1191 See P3.13.7.1.
P3.13.7.4
Setpoint 2 Max
Compensation
Varies Varies Varies Varies 1192
See P3.13.7.2.