Table 87: Feedback supervision parameters
Index Parameter Min Max Unit Default ID Description
P3.13.6.1
Enable Feedback
Supervision
0 1 0 735
0 = Disabled
1 = Enabled
P3.13.6.2
Upper Limit Varies Varies Varies Varies 736
The supervision of the
upper actual/process
value.
P3.13.6.3
Lower Limit Varies Varies Varies Varies 758
The supervision of the
lower actual/process
value.
P3.13.6.4 Delay 0 30000 s 0 737
If the target value is
not reached in this
time, a fault or alarm
shows.
P3.13.6.5
Response to PID
Supervision Fault
0 3 2 749
0 = No action
1 = Alarm
2 = Fault (Stop
according to stop
mode)
3 = Fault (Stop by
coasting)
PARAMETERS MENU VACON · 181