Table 86: Sleep function settings
Index Parameter Min Max Unit Default ID Description
P3.13.5.1
SP1 Sleep Frequency 0.00 320.00 Hz 0.00 1016
The drive goes to sleep
mode when the output
frequency stays below
this limit for a longer
time than set by SP1
Sleep Delay.
P3.13.5.2
SP1 Sleep Delay 0 300 s 0 1017
The minimum quantity
of time during which
the frequency has to
stay below the sleep
level before the drive
stops.
P3.13.5.3
SP1 Wake-up Level Varies 0.0000 1018
Gives the level for the
PID feedback value
wake-up supervision.
Uses the set process
units.
P3.13.5.4
SP1 Wake-up Mode 0 1 0 1019
The selection for the
operation of P3.13.5.3.
0 = Absolute level
1 = Relative setpoint
P3.13.5.5
SP2 Sleep Frequency 0.00 320.00 Hz 0.00 1075
See P3.13.5.1.
P3.13.5.6
SP2 Sleep Delay 0 3000 s 0 1076
See P3.13.5.2.
P3.13.5.7
SP2 Wake-up Level Varies 0.0000 1077
See P3.13.5.3.
P3.13.5.8
SP2 Wake-up Mode 0 1 0 1020
The selection for the
operation of P3.13.5.7.
0 = Absolute level
1 = Relative setpoint
VACON · 180 PARAMETERS MENU