Table 84: Feedback settings
Index Parameter Min Max Unit Default ID Description
P3.13.3.5
Feedback 1
Maximum
-200.00 200.00 % 100.00 337
The maximum value at
the analogue signal
maximum.
P3.13.3.6
Feedback 2 Source
Selection
0 20 0 335
See P3.13.3.3.
P3.13.3.7 Feedback 2 Minimum -200.00 200.00 % 0.00 338
The minimum value at
the analogue signal
minimum.
M3.13.3.8
Feedback 2
Maximum
-200.00 200.00 % 100.00 339
The maximum value at
the analogue signal
maximum.
* = The selection of the application with parameter P1.2 Application gives the default value.
See the default values in Chapter 11 Appendix 1.
Table 85: Feedforward settings
Index Parameter Min Max Unit Default ID Description
P3.13.4.1
Feedforward
Function
1 9 1 1059
See P3.13.3.1
P3.13.4.2
Feedforward
Function Gain
-1000 1000 % 100.0 1060
See P3.13.3.2
P3.13.4.3
Feedforward 1
Source Selection
0 25 0 1061
See P3.13.3.3
P3.13.4.4
Feedforward 1
Minimum
-200.00 200.00 % 0.00 1062
See P3.13.3.4
P3.13.4.5
Feedforward 1
Maximum
-200.00 200.00 % 100.00 1063
See P3.13.3.5
P3.13.4.6
Feedforward 2
Source Selection
0 25 0 1064
See P3.13.3.6
P3.13.4.7 Feedforward 2 Min -200.00 200.00 % 0.00 1065 See P3.13.3.7
P3.13.4.8 Feedforward 2 Max -200.00 200.00 % 100.00 1066 See M3.13.3.8