Table 84: Feedback settings
Index Parameter Min Max Unit Default ID Description
P3.13.3.3
Feedback 1 Source
Selection
0 30 2 * 334
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI5
6 = AI6
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
15 = Temperature input 1
16 = Temperature input 2
17 = Temperature input 3
18 = Temperature input 4
19 = Temperature input 5
20 = Temperature input 6
21 = Block Out.1
22 = Block Out.2
23 = Block Out.3
24 = Block Out.4
25 = Block Out.5
26 = Block Out.6
27 = Block Out.7
28 = Block Out.8
29 = Block Out.9
30 = Block Out.10
The AIs and the
ProcessDataIn are
handled as percentage
(0.00-100.00%) and
scaled according to
Feedback minimum and
maximum.
NOTE!
The ProcessDataIn
signals use 2 decimals.
If you set temperature
inputs, you must set the
setpoint minimum and
maximum scaling
parameters between -50
and 200 °C.
P3.13.3.4
Feedback 1 Minimum -200.00 200.00 % 0.00 336
The minimum value at
the analogue signal
minimum.